Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Manual Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Item
|
Description
|
Unit
|
Data
|
|
1
|
Rated voltage
|
KV
|
24
|
|
2
|
Max. voltage
|
KV
|
24
|
|
3
|
Rated current
|
A
|
630/1250/2500
|
|
4
|
Rated short circuit breaking current
|
KA
|
20/25/31.5
|
|
5
|
Rated short circuit making current
|
KA
|
50/63/80
|
|
6
|
Rated peak withstand current
|
KA
|
50/63/80
|
|
7
|
4S Rated withstand current
|
KA
|
20/25/31.5
|
|
8
|
Rated insulation level |
Power frequency voltage(when losing a circuit)
|
KV
|
Dreaker 65
|
Impulse withstand voltage(when losing a circuit)
|
Dreaker 125
|
|||
9
|
Rated operating sequence
|
|
OC-0.3s-CO-180S-CO
|
|
10
|
Mechanical life
|
Times
|
20000
|
|
11
|
Rated short circuit current breaking time
|
Times
|
274
|
|
12
|
Rated close brake voltage of operating machnie
|
V
|
110,220
|
|
13
|
Rated break brake voltage of operating machnie
|
V
|
110,220
|
|
14
|
Contact stroke
|
mm
|
13±1
|
|
15
|
Exceed range(the compress length of contact sping)
|
mm
|
3.5±0.5
|
|
16
|
Different period of three-phase break and close break
|
ms
|
≤2
|
|
17
|
The jump time of contact close break
|
ms
|
≤2
|
|
18
|
Average break speed
|
m/s
|
1.1~1.7
|
|
19
|
Average closing speed
|
m/s
|
0.6~1.1
|
|
20
|
Opening time |
Ubder max.operating voltage
|
S
|
≤0.05
|
Under min.operating voltage
|
≤0.08
|
|||
21
|
Closing time
|
s
|
0.1
|
|
22
|
Resistance of each phase main loop
|
μΩ
|
630≤50 1250≤45/ 1600-2500≤40
|
|
23
|
Contacts limit ersion
|
mm
|
3
|