Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Manual Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Serial Number | Project | Nuit | Data | ||
1 | Rated voltage | KV | 12 | ||
2 | Rated frequency | Hz | 50 | ||
3 | Current rating | A | 630 | 1000 | |
4 | Rated short-time interrupting current | KA | 20 | 25 | |
5 | Rated peak withstand current | KA | 50 | 63 | |
6 | Rated short-time withstand current | KA | 20 | 25 | |
7 | Rated short-circuit closing current | KA | 50 | 63 | |
8 | Rated sequence of operations | min-0.3s-combine-180s-combine | |||
9 | Rated short-circuit duration | S | 4 | ||
10 | Mechanical life | times | 10000 | ||
11 | The number of times the rated current is interrupted | times | 10000 | ||
12 | Rated number of short circuit breaks | times | 30 | ||
13 | Power frequency withstand voltage(1min) | (wet) phase, to the ground | KV | 34 | |
(Dry) interphase,ground/fracture | KV | 42/48 | |||
14 | Withstand lightning impulse voltage interphase, ground/fracture | KV | 75/78 | ||
15 | The secondary circuit has a power frequency withstand voltage of 1min | V | 20000 |